| Description RAF 80Q is a piloted hydraulic valve activated by line pressure. The two-way pilot valve has a spring-loaded membrane which is sensitive to upstream pressure. The RAF 80Q is normally closed. As line pressure rises above the preset level, the valve opens quickly to relieve the excessive pressure. |
Available Models RAF 80Q - General Application two-way Pressure Relief valve. Pressure rating up to 16 bars. The RAF 80Q is supplied in two standard configurations, both with metal pilots: small sizes (up to 4) & medium size (6-12). |
|
| Applications Use RAF 80Q for general water supply systems with medium pressure rating. The elaborated two-way pilot with Raphaels patented diaphragm enables smooth & precise pressure control. Quick pressure relief valve protects water systems from quickly rising excessive pressure, due to water hammer surge. It is recommended to install RAF 80Q at the system head, right next to the main supply line or booster pump. |
||
| Installation RAF 80Q Quick Pressure Relief Valve is activated by line pressure & controlled by a pilot valve. The pilot includes a spring-loaded membrane which is exposed to line pressure. The displacement of the membrane due to a rise of line pressure against the spring force changes the water flow inside the pilot. The RAF 80Q is normally closed. Only when the line pressure is higher than the preset value, the RAF 80Q is piloted to open. |
||
| RAF
80Q - Quick Pressure Relief Valve |
||
|
Typical Application
|
|
| Adjustment Use the needle valve a to control the RAF 68 operational speed. Adjust pressure set points by the adjusting screws of the pilots. See the list of available springs on the next page. |
||
Quick Pressure Relief Valve |
Configuration |
Model |
Please Specify:
|
Two way Pilots |
RAF 80Q |
| Standard RAF 80Q Size 2"-4" | Standard RAF 80Q Size 6"-12" | Special Features |
| Complete basic RAF valve as specified above | Complete basic RAF valve as specified above |
Enamel/epoxy coating |
| Self-cleaning screen filter | Self-cleaning screen filter |
External heavy duty screen filter |
| Metal pilot | Metal pilot upon request | - |
| 3/8" Reinforced Plastic tubes | 8 mm Plastic tubes | Copper or stainless steel tubes |
| Metal Pilot |
| Body & bonnet- Brass Spring-Music wire. Membrane-Nylon fabric reinforced Natural Rubber. Bolts & nuts-Zinc plated steel. Pressure rating: up to 12 bar |
![]() |
|||
| Description | Applications | Available Models | Installation | | Typical Application | Specification Form | |
![]() |
||
| RAPHAEL
Valves Industries (1975) LTD. N. Ind. Zone, P.O.Box 555, Or-Aqiva 30600,Israel. Tel. 972-4-6263555, Fax. 972-4-6263558 e-mail |